RISH Ducer : Current E15
 
Features :
  Designed and Tested to meet Requirements of IEC 688 and IS 12784
  Reliable SMD Technology
  High Insulation Level
  Higher load Capacity
  Easy onsite conversion between DIN rail or Panel Mounting
  Polycarbonate body, conforming to UL 94-VO
     
 
Measuring Quantity
AC Current
Nominal Input
1/1.2/5 or 6A
Output Quantity
Independent DC Current or DC Voltage
Output Range
0...10V/1...5V0...1/5/10/20mA or 4-20mA Option: Dual Output
Ripple
<1% P-P
Output Burden
Current Output : Rext = 15V / I (full  Scale) [750 @ 20mA or 1500  @ 10mA]
Voltage Output : Rext = Output Voltage/ 20mA,
Auxiliary supply
AC 24V/115V/120V/230V/
240V/250V DC 24V/48V/60V or 110V
Power Consumption
< 0.2 VA in Current < 1VA in Voltage
Response Time
< 300ms
High Insulation Level
4 kV
Impulse withstand Voltage
5kV, 1.2/50 µsec, 0.5 Ws.
Accuracy as per IEC 688
Class 0.5
Operating Temperature
-25 to 55°C
     
   
  - M42
  - M24
  - M40
  - M01
  - M20
  - Configuration Software MXX
  - I 11
  - I 12
  - E 15
  - E 1D
  - E 13
  - I 21
  - I 22
  - V 11
  - E 15
  - E 1D
  - E 13
  - V 21
  - V 22
  - F 11
  - F 12
  - P11- Active/Reactive
  - C11-Powe Factor/Phase Angle
  - C12- Phase angle difference