A.C. Voltage Relay with adjustable time delay
 
Application :
  The Rishabh A.C. Voltage Protectors provide continuous surveillance of the monitored circuit. When the measured voltage moves outside the set point limit, the relay will operate giving an alarm and or initiation signal. An illuminated LED indicates when the relay is energised. The 3 phase, 3 or 4 wire models protect each phase independently.
  The Protector can be used to protect for:
  Under voltage
  Over current
  Start up standby generators
  Operation of mains failure units
  Switching standby hybrid supplies
  Protecting computer supplies
  Where close control is require
   
  Features :
  Adjustable set point
  Adjustable time delay
  Internal differential
  LED trip indication
  2 pole relay contacts
     
  Specifications :
 
Input :
Nominal current 100, 110, 220, 230, 240, 380, 400, 415 or 440V (57 to 480V)
System Frequency 45/65Hz or 360/440Hz
Overload 1.2 x continuously
1.5 x for 10 x 10 seconds
To BS 6253
Set Point :
Repeatability Better than 0.5%
Differential Preset at 1% Other values 1% to 10% (specify)
Adjustable Range Under Voltage 75 to 100%
Over Voltage 100 to 125%
of nominal input voltage
Time Delay Adjustable up to 10 seconds.
30 seconds maximum
Burden 3VA
Weight 252 case - approx 0.4Kg
253 case - approx 0.6Kg
Output Relay :
Type D.P. Changeover
Rating A.C 240V,5A non-inductive
  D.C
View chart
Operations 0.2 million at the above loads
Reset Automatic
 
   
  - Protector Trip Relays
  - A.C. Current Relay
  - A.C. Voltage Relay with adjustable differential
  - A.C. Voltage Relay with adjustable time delay
  - Frequency Relay
  - Combined Under / Over Voltage & Under / Over Frequency Relay
  - Phase Sequence & Phase Failure Relay
  - Phase Balance Relay
  - Reverse Power (Current) Relay
  - Synchro-Check Relay(Paralleling)
  - D.C. Voltage Relay
  - Thermistor Trip Relay
  - Hot Spot 3 Relay
  - Hot Spot 6 Relay
  - Millivolt / Thermocouple Relay
  - Transducer Trip
  - Speed Sensing Trip Relay