| Input |
Up to six RTD sensors e.g. 100W platinum
(Pt100) or 10W copper |
| Ambient Temperature |
0 to 60°C |
| Adjustment Range |
100°C (e.g. 50 to 150°C,100 to
200°C etc) |
| User Adjustment |
Screwdriver adjustable, multi-turn potentiometer, access on front panel.
Approximately 5°C per turn. Turn anti-clockwise to raise trip point. |
| Operating Time |
<100ms |
| Repeatability |
within 1°C |
| Reset |
Automatic. Relay differential
(pull-in to drop-out) 4°C nominal |
| Auxiliary supply |
A.C. 50/60Hz , 110, 120, 220, 230, 240V +20% (specify) |
| Burden |
6 VA maximum |
| Weight |
Approximately 1.4Kg |
| Output Relay : |
| Type |
Single Pole Changeover |
| Rating A.C |
240V,5A non-inductive |
|
View chart |
| Operations |
0.2 million at the above load |
| Reset |
Automatic |