| Input : |
| D.C. millivolts |
Spans 10mV(min), 50mV, 60mV,
75mV, 100mV, 150mV |
| Overload |
10 x continuously |
| Input Impedance |
Approximately 50kW |
| Source Impedance |
Maximum 100W |
| Thermocouple |
Types J, K, R, S, T Minimum span 10mV
Maximum span 50mV |
| Thermocouple Break Protection(TBP) |
Upscale drive is standard |
| Cold Junction Compensation : |
| (CJC) |
Available on application |
| Set point |
|
| Repeatability |
0.5% of span |
| Hysteresis |
2 % of span |
| Adjustment |
Low trip 0-80%
High trip : 40-120% |
| Time Delay |
Up to 10 seconds adjustable
30 seconds maximum |
| Auxiliary Supply : |
| A.C. 50/60 Hz |
120V or 240V (+20%) (57 to 480V) |
| D.C. Voltage |
12, 24,48 or 120V (+20%) |
| Burden |
3 VA maximum |
| Weight |
Approximately 0.4Kg |
| Voltage Withstand |
1.2 x continuously
1.5 x for 10 x 10 seconds to B.S. 6253 |
| Output Relay : |
| Type |
DP Changeover |
| Rating A.C |
240V,5A non-inductive |
|
View chart |
| Operations |
0.2 million at the above load |
| Reset |
Automatic |