| System |
3 phase, 3 or 4 wire |
| Frequency |
50 or 60Hz |
| Nominal Voltage |
100, 110, 120, 220, 230, 240, 380, 400, 415 & 440V (57 to 480V) |
| Burden |
3VA |
| Voltage Withstand |
1.2 x continuously
1.5 x for 10 x 10 seconds |
| Set Point : |
| Unbalance |
Adjustable 5% to 15% |
| Time Delay |
Up to 10 seconds adjustable, 30 seconds maximum (not operative if voltage falls below 70% of the nominal voltage or set point on
type 252-PSG) |
| Under Voltage |
(Type 252-PSG only) Internally preset at 15% of nominal voltage (other values between 10% and 30% available on request) |
| Weight |
Approximately - 0.3 kg |
| Output Relay : |
| Type |
D.P. Changeover |
| Rating A.C |
240V,5A non-inductive |
|
View chart |
| Operations |
0.2 million at the above loads |
| Reset |
Automatic |